: Carefully disconnect field wiring from the legacy CPU and Power/Comm boards. : Mount the LNL-3300-M5
Sets the downstream RS-485 port speed to communicate with MSeries interface boards. 9600 Baud: 6 OFF, 7 OFF 19200 Baud: 6 ON, 7 OFF 38400 Baud: 6 OFF, 7 ON Switch 8 (Reserved): Typically left in the OFF position. S2 DIP Switch Settings (Memory and Operational Modes)
By default, the board may be set to DHCP or a default static IP (check the manual for current default settings). lenel lnl3300m5 installation manual upd top
is part of the Series 3 intelligent controller lineup. It is designed to be highly flexible, offering onboard reader ports, input/output points, and support for additional downstream modules (like LNL-1320, LNL-1100, etc.). Capacity: Supports up to 240,000 cardholders. Networking: Native 10/100 Ethernet communication. Downstream Support: Supports up to 32 downstream devices.
Lenel LNL-3300-M5 is an Intelligent System Controller (ISC) designed specifically as a plug-compatible replacement for legacy CASI M5 and M3000 CPU boards, facilitating a seamless migration to the OnGuard security system. Hitron Bina Teknolojileri Installation & Configuration Overview : Carefully disconnect field wiring from the legacy
The "M Series Installation Guide," formally designated as DOC-1042-EN-US, is the authoritative resource for the hardware installation of the LNL-3300-M5. This guide aims to be the "updated top" resource for integrators, merging official hardware documentation, wiring specifics, configuration settings, firmware updates, and system troubleshooting from the latest revisions of the official manual and other technical sources.
: Use a web browser to navigate to 192.168.0.251 . Turn DIP switch 1 ON and log in with the default username admin and password password . S2 DIP Switch Settings (Memory and Operational Modes)
The Lenel LNL‑3300‑M5 is the central processing unit for the Lenel M Series controller enclosure. It is designed to work with the OnGuard access control and alarm management platform. The controller uses distributed processing, meaning many critical access decisions are made locally at the controller rather than relying on a central host, which significantly reduces network latency and improves system reliability.
Locate the primary AC breaker or DC fuse feeding the Micro/5 enclosure and disconnect power before touching any boards.